Siemens Mag Flow Meters and Transmitter Configurations for SCADA Integration
Quick Answer: Siemens mag flow meters connect to SCADA through 4-20 mA HART, pulse, Modbus RTU, or PROFIBUS DP. Most plants get reliable signals with 4-20 mA HART, damping set to 1-3 seconds, and the shield grounded at one end only. Silver Automation Instruments supplies compatible mag flow meters and pre-sets transmitter settings for your SCADA tags.
Siemens Mag Flow Meter Models and SCADA Integrated Elements
Many water plants run SITRANS FM MAG 5100 W flow tubes with MAG 6000 transmitters. The MAG 6000 supports 4-20 mA, HART, pulse, and internal totalizers. Some networks use the battery powered MAG 8000 for district metering and irrigation. The SCADA integrated elements on these meters include analog current output, pulse frequency output, digital communication port, and alarm flags for empty pipe or high flow.
Silver Automation Instruments stocks electromagnetic flow meters from DN15 to DN2000. We often replace failed sensors or transmitters without changing the SCADA address map. A customer in Vietnam recently replaced a DN150 raw water meter with one of our remote style mag meters. The PLC kept the same 4-20 mA scaling from 0 to 180 m3 per hour.
Siemens Mag Flow Transmitter Configurations That Field Engineers Use
Configuration depends on the SCADA protocol. For a simple flow reading on a PLC analog input, use 4-20 mA with HART. For totalized volume, use a pulse output into a digital input. For Modbus RTU networks, the RS-485 terminals on a MAG 6000 or compatible transmitter carry flow rate, totalizer, and diagnostic data on two wires.
Here is a practical list for field engineers:
- 4-20 mA HART for analog loops and legacy PLC cards
- Pulse output for batch control and totalizer display
- Modbus RTU over RS-485 for multi-drop SCADA and telemetry
- PROFIBUS DP for Siemens PLC networks and large plants
Most engineers skip PROFIBUS unless the plant already has a DP segment. For new remote sites, Modbus RTU is easier to test with a laptop and a USB to RS-485 adapter.
Settings That Prevent SCADA Signal Problems
In practice, a bad damping setting causes more SCADA alarms than sensor failure. Set damping to 1 to 3 seconds for raw water flow. Use 5 to 10 seconds for sludge or chemical dosing lines where flow pulses. Set the low flow cut off near 0.1 m per second to stop zero drift. Set the 4 mA value at zero flow and the 20 mA value at your maximum expected flow. Keep the maximum flow at 110 to 120 percent of the normal pipe capacity.
For Modbus RTU, set the device address from 1 to 247. Use 9600 or 19200 baud and even parity as a starting point. Match the PLC port settings before testing the loop.
For pulse output, choose a pulse volume that does not exceed the PLC scan time. A DN100 meter with a flow range of 0 to 100 m3 per hour can send one pulse per 0.1 m3. The pulse rate comes to about 0.28 pulses per second at normal flow. A paint manufacturer in Southeast Asia used a pulse per liter setting and flooded the PLC input. We changed the pulse value to one pulse per 10 liters and solved the problem without rewiring.
Wiring and Grounding for SCADA Reliability
Use shielded twisted pair cable for 4-20 mA and Modbus runs. Earth the shield at the PLC end only. Do not ground both ends. Grounding both ends creates a ground loop. For long runs above 100 meters, use a loop isolator for 4-20 mA and 120 ohm termination at the last Modbus device. Separate signal cable from VFD motor cables by at least 300 mm in cable trays.
For ATEX Zone 1 areas, use a remote transmitter and keep the converter outside the hazard area if possible. A remote transmitter keeps hot work and commissioning simpler.
We have seen customer sites in the Philippines where flow readings jumped every time a pump

Current position >About Us